Appendix F: PX3 Models with Residual Current Monitoring
718
Setting Front Panel RCM Self-Test
You can enable or disable the front panel RCM self-test function via CLI
in addition to the web interface.
To enable the front panel RCM self-test:
#
security frontPanelPermissions add rcmSelfTest
To disable the front panel RCM self-test:
#
security frontPanelPermissions remove rcmSelfTest
Running RCM Self-Test
You can perform RCM self-test for a specific inlet via CLI. After the
self-test finishes, the test result is shown: pass or fail.
To perform RCM self-test:
#
rcm selfTest inlet <n>
Variables:
<n> is the inlet's number. For a single-inlet PDU, <n> is always 1.
Degaussing RCM Type B Sensors
Only the models with RCM 'Type B' sensors support degaussing the RCM
sensors. Those with RCM Type A sensors do NOT support this feature.
You can degauss the RCM sensor after a current surge, such as a short
circuit.
To degauss RCM Type B sensors:
#
rcm degauss
Содержание PX3-3000 series
Страница 5: ......
Страница 18: ...Contents xviii Index 841...
Страница 66: ...Chapter 3 Initial Installation and Configuration 42 Number Device role Master device Slave 1 Slave 2 Slave 3...
Страница 93: ...Chapter 4 Connecting External Equipment Optional 69...
Страница 787: ...Appendix J RADIUS Configuration Illustration 763 Note If your PX3 uses PAP then select PAP...
Страница 788: ...Appendix J RADIUS Configuration Illustration 764 10 Select Standard to the left of the dialog and then click Add...
Страница 789: ...Appendix J RADIUS Configuration Illustration 765 11 Select Filter Id from the list of attributes and click Add...
Страница 792: ...Appendix J RADIUS Configuration Illustration 768 14 The new attribute is added Click OK...
Страница 793: ...Appendix J RADIUS Configuration Illustration 769 15 Click Next to continue...
Страница 823: ...Appendix K Additional PX3 Information 799...
Страница 853: ...Appendix L Integration 829 3 Click OK...