Chapter 3: Initial Installation and Configuration
50
Supported Sensor Configurations for Power Sharing
All information and restrictions described in this section apply to
BOTH PDUs involved in the power-sharing configuration, unless
otherwise specified.
There are no limitations for connecting Raritan's DPX or DPX2
environmental sensor packages to an iX7
™
PDU in the power-sharing
mode. See
DPX Sensor Packages
(on page 53) or
DPX2 Sensor
Packages
(on page 58).
The maximum number of supported DPX3 environmental sensor
packages remains unchanged -- that is, 12 DPX3 packages. See
DPX3
Sensor Packages
(on page 60).
The maximum number of supported DX environmental sensor packages
also remains unchanged as long as the DPX3-ENVHUB4 sensor hub is
not used -- that is, 12 DX sensor packages. See
DX or DX2 Sensor
Packages
(on page 62).
However, there are DX restrictions when DPX3-ENVHUB4 is used, and
there are also door handles-related restrictions.
DX sensor restrictions when connected via DPX3-ENVHUB4:
A maximum of one DPX3-ENVHUB4 and a maximum of 10 DX sensor
packages are supported.
Restrictions of connecting door handles via DX-PD2C5:
A maximum of 4 handles connected to a maximum of two DX-PD2C5
packages are supported.
All of the 4 handles must be controlled by the same PDU to ensure
that only one handle is in the unlocked state at a time. That is, the
door handles are connected to only one PDU in the power-sharing
connection, NOT both.
When more than one DX-PD2C5 are required, they must be cascaded
via standard network patch cables, instead of using a sensor hub.
Other sensor restrictions when door handles are present:
Make sure the connection of door handles complies with the above
restrictions.
Содержание PX3-3000 series
Страница 5: ......
Страница 18: ...Contents xviii Index 841...
Страница 66: ...Chapter 3 Initial Installation and Configuration 42 Number Device role Master device Slave 1 Slave 2 Slave 3...
Страница 93: ...Chapter 4 Connecting External Equipment Optional 69...
Страница 787: ...Appendix J RADIUS Configuration Illustration 763 Note If your PX3 uses PAP then select PAP...
Страница 788: ...Appendix J RADIUS Configuration Illustration 764 10 Select Standard to the left of the dialog and then click Add...
Страница 789: ...Appendix J RADIUS Configuration Illustration 765 11 Select Filter Id from the list of attributes and click Add...
Страница 792: ...Appendix J RADIUS Configuration Illustration 768 14 The new attribute is added Click OK...
Страница 793: ...Appendix J RADIUS Configuration Illustration 769 15 Click Next to continue...
Страница 823: ...Appendix K Additional PX3 Information 799...
Страница 853: ...Appendix L Integration 829 3 Click OK...