Chapter 2: Rackmount, Inlet and Outlet Connections
13
4.
Screw a button in the screw hole near the top. The recommended
torque for the button is 1.96 N·m (20 kgf·cm).
5.
Ensure that the two buttons can engage their mounting holes in the
rack or cabinet simultaneously.
6.
Press the PX3 device forward, pushing the mounting buttons through
the mounting holes, then letting the device drop slightly. This
secures the PX3 device in place and completes the installation.
Mounting 1U or 2U Models
Using the appropriate brackets and tools, fasten the 1U or 2U device to
the rack or cabinet.
To mount the PX3 device:
1.
Attach a rackmount bracket to both sides of the PX3 with the
provided screws.
2.
Insert the cable-support bar into rackmount brackets.
Содержание PX3-3000 series
Страница 5: ......
Страница 18: ...Contents xviii Index 841...
Страница 66: ...Chapter 3 Initial Installation and Configuration 42 Number Device role Master device Slave 1 Slave 2 Slave 3...
Страница 93: ...Chapter 4 Connecting External Equipment Optional 69...
Страница 787: ...Appendix J RADIUS Configuration Illustration 763 Note If your PX3 uses PAP then select PAP...
Страница 788: ...Appendix J RADIUS Configuration Illustration 764 10 Select Standard to the left of the dialog and then click Add...
Страница 789: ...Appendix J RADIUS Configuration Illustration 765 11 Select Filter Id from the list of attributes and click Add...
Страница 792: ...Appendix J RADIUS Configuration Illustration 768 14 The new attribute is added Click OK...
Страница 793: ...Appendix J RADIUS Configuration Illustration 769 15 Click Next to continue...
Страница 823: ...Appendix K Additional PX3 Information 799...
Страница 853: ...Appendix L Integration 829 3 Click OK...