Installation
Section 3-2
CPU Bus Unit Allocated
DM Area (DM Parameter
Area)
The DM area is allocated 100 words for each unit number starting from the
words D30000.
3-2
Installation
3-2-1
System Configuration Precautions
CJ1W-MCH71
• When using the IOWR/IORD instructions for the MC Unit, be sure that a
version 2.0 or later CJ1-H/CJ1M CPU Unit is being used.
• I/O bit numbers of the CPU Bus Unit are allocated based on the setting of
the Unit Number Setting Switch on the front panel of the Unit, not on the
position in which the Unit has been connected.
• MC Units can be connected in either the CPU Rack or in Expansion
Racks. A maximum of 3 MC Units can be connected per Rack. The total
number of MC Units for the CPU Rack and all Expansion Racks is thus 12
MC Units maximum.
• When mounting a relay output unit on the very right of the MC Unit, make
sure to use the surge absorber for the relay output line.
When MECHATROLINK-II devices are connected up to 16 nodes (within
30 m) or 15 nodes (within 50 m), no repeater unit is required. A repeater unit
is required to connect MECHATROLINK-II devices more than the cases
above.
CS1W-MCH71
• When using the IOWR/IORD instructions for the MC Unit, be sure that the
CS1
@
-CPU
@@
H CPU Unit being used was manufactured on April 18,
2003 (Lot No. 030418) or later.
• The I/O words allocated to a CPU Bus Unit are based on the setting of the
unit number setting switch on the front panel of the Unit, not on the posi-
tion in which the Unit has been mounted.
• The Units can be mounted to the CS1W-BC
@@
3 or CS1W-BC
@@
2 CPU
Backplane, or the CS1W-BI
@@
3 or CS1W-BI
@@
2 Expansion Backplane.
Unit number
DM area
Unit number
DM area
0
Words 30000-30099
8
Words 30800-30899
1
Words 30100-30199
9
Words 30900-30999
2
Words 30200-30299
10
Words 31000-31099
3
Words 30300-30399
11
Words 31100-31199
4
Words 30400-30499
12
Words 31200-31299
5
Words 30500-30599
13
Words 31300-31399
6
Words 30600-30699
14
Words 31400-31499
7
Words 30700-30799
15
Words 31500-31599
MC Unit
Make sure to use the surge absorber for the
contact output of this relay output unit.
Содержание CS1W-MCH71 -
Страница 2: ...CS1W MCH71 CJ1W MCH71 Motion Control Unit Operation Manual Revised June 2008 ...
Страница 3: ...iv ...
Страница 29: ...xxx ...
Страница 33: ...xxxiv ...
Страница 35: ...xxxvi ...
Страница 39: ...xl ...
Страница 69: ...24 Performance Section 1 7 ...
Страница 99: ...54 Connecting MECHATROLINK Devices Section 3 5 ...
Страница 283: ...238 Saving Data Section 5 4 ...
Страница 417: ...372 Command Details Section 6 3 ...