![Omron CS1W-MCH71 - Скачать руководство пользователя страница 447](http://html1.mh-extra.com/html/omron/cs1w-mch71/cs1w-mch71_operation-manual_742367447.webp)
402
Allocations for the CPU Unit
Section 7-3
7-3-2
DM Area Words for Unit (20 Words, CPU Unit
→
MC Unit)
Default Setting Area
DM Output Area for the Unit (CPU
→
MC Unit, 20 Words)
Classification
Word
Variable
bit
Name
Specifications
Unit area range
settings
(First time only)
m
---
00-15
Bit Area Type
Specifies area type on CPU Unit
0: Not used (no transfer)
1: CIO
2: WR
3 and above: Reserved for system
m+1
---
00-15
Bit Area First
Address
Specifies the first address on CPU Unit (Allocation
for the axis number 1)
0000H-(Upper limit varies depending on bit area
type.)
Note
The transfer size is maximum effective axis
number x 2 words
m+2
---
00-15
Data Area Type
Specifies area type on CPU Unit
0: Not used (no transfer)
1: CIO
2: WR
3: DM
4: EM (fixed at Bank 0)
5 and above: Reserved for system
m+3
---
00-15
Data Area First
Address
Specifies the first address on CPU Unit (Allocation
of the axis number 1)
0000H-(Upper limit varies depending on bit area
type.)
Note
The transfer size is maximum effective axis
number x 4 words)
General I/O A
area range set-
tings
(First time only)
m+4
---
00-07
PORT_A Number of
Transferred Words
General I/O A Number of Transferred Words
1-160 words
08-14
PORT_A Area Type
Specifies area type on CPU Unit
0: Not used (no transfer)
1: CIO
2: WR
3: DM
4: EM (fixed at Bank 0)
5 and above: Reserved for system
15
PORT_A Direction
General I/O A Transfer Direction
0: MC Unit
→
CPU
1: CPU
→
MC Unit
m+5
---
0-15
PORT_A First
Address
CPU Unit First Address for General I/O A
0000H-(Upper limit varies depending on PORT_A
area type.)
General I/O B
area range set-
tings
m+6
---
Same as for General I/O A area range settings
m+7
General I/O C
area range set-
tings
m+8
---
Same as for General I/O A area range settings
m+9
General I/O D
area range set-
tings
m+10
---
Same as for General I/O A area range settings
m+11
General I/O E
area range set-
tings
m+12
---
Same as for General I/O A area range settings
m+13
Содержание CS1W-MCH71 -
Страница 2: ...CS1W MCH71 CJ1W MCH71 Motion Control Unit Operation Manual Revised June 2008 ...
Страница 3: ...iv ...
Страница 29: ...xxx ...
Страница 33: ...xxxiv ...
Страница 35: ...xxxvi ...
Страница 39: ...xl ...
Страница 69: ...24 Performance Section 1 7 ...
Страница 99: ...54 Connecting MECHATROLINK Devices Section 3 5 ...
Страница 283: ...238 Saving Data Section 5 4 ...
Страница 417: ...372 Command Details Section 6 3 ...