![Omron CS1W-MCH71 - Скачать руководство пользователя страница 685](http://html1.mh-extra.com/html/omron/cs1w-mch71/cs1w-mch71_operation-manual_742367685.webp)
640
Unit-related Alarm Codes
Section 11-4
PLC WDT error
0001h
0000h
0030h
WDT error on CPU Unit occurred.
Follow the instructions in the appli-
cable PLC manual.
Any time
System
stop
Disabled
PLC cyclic ser-
vice monitor error
0002h
Monitor
Time
[ms]
0031h
CPU Unit did not execute end
refresh processing within cyclic
service monitor time.
Check end refresh prohibition in
CPU system setup. If prohibited,
cancel it and turn the power OFF
once, and then ON again.
Increase CPU Unit cyclic service
monitor time and turn the power
OFF once, then ON again.
Any time
Decelera-
tion stop
Disabled
Bus error
(PC21bus error)
000Eh
0000h
0032h
Bus error occurred between CPU
Unit and MC Unit.
Any time
System
stop
(Including
event)
Disabled
CPU fatal error
0015h
0000h
0033h
CPU fatal error occurred.
Follow the instructions in the appli-
cable PLC manual.
Any time
System
stop
Disabled
CPU non-fatal
error
0016h
0000h
---
Follow the instructions in the appli-
cable PLC manual.
Any time
---
---
Name
Error log
Alarm
code
Cause and remedy
Timing
Rank
Reset
Error
code
Detail
code
Содержание CS1W-MCH71 -
Страница 2: ...CS1W MCH71 CJ1W MCH71 Motion Control Unit Operation Manual Revised June 2008 ...
Страница 3: ...iv ...
Страница 29: ...xxx ...
Страница 33: ...xxxiv ...
Страница 35: ...xxxvi ...
Страница 39: ...xl ...
Страница 69: ...24 Performance Section 1 7 ...
Страница 99: ...54 Connecting MECHATROLINK Devices Section 3 5 ...
Страница 283: ...238 Saving Data Section 5 4 ...
Страница 417: ...372 Command Details Section 6 3 ...