649
Axis-related Alarm Codes
Section 11-6
Software limit
negative
direction
037Ah
-
0399h
3006h
3006h
• The axis entered the software limit area in
negative direction during axis movement
with the origin defined. Check if the set-
ting value of the axis parameter [P3AA02:
Negative direction software limit] is cor-
rect. (The error may occur when execut-
ing circular interpolation right on the
software limit values.) If the setting value
is incorrect, set a larger limit value. When
the value is correct, correct the program
or travel distance of the axis.
Any time
Decelera-
tion stop
Enabled
Servo OFF
3007h
3007h
• The axis that received a movement com-
mand is in Servo OFF state. (In opera-
tions with programs, this alarm will occur
when the applicable axis is specified at
the beginning of the block and a move-
ment command is executed for the axis
that is in Servo OFF state.) Switch the
axis to Servo lock state.
• Servo OFF was executed for the axis
receiving a movement command.
Do not execute Servo Unlock during axis
movement.
When
axis
move-
ment
starts/
During
axis
move-
ment.
Servo OFF Enabled
Synchronous
communica-
tions alarm
300Ah
300Ah
An error was occurred in the MECHA-
TROLINK synchronous communications.
The followings are the possible causes:
• Disconnection, breakage of MECHA-
TROLINK cable
Check the MECHATROLINK cable.
• Communications error caused by noise
Remove the cause of the noise.
When this error persists even after provid-
ing these remedies, the Driver (NS115) or
MC Unit may be broken. Replace the bro-
ken one with a new unit.
Any time
Servo OFF Enabled
Communica-
tions alarm
300Bh
300Bh
Detected MECHATROLINK communica-
tions errors twice in a row. Or the No. of
error detections specified in [P1AA06:
MECHATROLINK-II communications error
detection setting] has been exceeded. The
followings are the possible causes:
• Disconnection, breakage of MECHA-
TROLINK cable
Check the MECHATROLINK cable.
• Communications error caused by noise
Remove the cause of the noise.
When this error persists even after provid-
ing these remedies, the Driver (NS115) or
MC Unit may be broken. Replace the bro-
ken one with a new unit.
Any time
Servo OFF Enabled
Name
Error log
Alarm
code
Cause and remedy
Timing
Rank
Reset
Error
code
Detail
code
Содержание CS1W-MCH71 -
Страница 2: ...CS1W MCH71 CJ1W MCH71 Motion Control Unit Operation Manual Revised June 2008 ...
Страница 3: ...iv ...
Страница 29: ...xxx ...
Страница 33: ...xxxiv ...
Страница 35: ...xxxvi ...
Страница 39: ...xl ...
Страница 69: ...24 Performance Section 1 7 ...
Страница 99: ...54 Connecting MECHATROLINK Devices Section 3 5 ...
Страница 283: ...238 Saving Data Section 5 4 ...
Страница 417: ...372 Command Details Section 6 3 ...