![Omron CS1W-MCH71 - Скачать руководство пользователя страница 708](http://html1.mh-extra.com/html/omron/cs1w-mch71/cs1w-mch71_operation-manual_742367708.webp)
663
Appendix A
Performance
Item
Performance (ms)
Description
Power ON startup time
Approximately (13 + 0.1
×
No.
of physical axes)
×
1000
Time from turning ON the power until the MC
Unit becomes ready to accept manual operation
commands, such as Servo Lock commands. Vir-
tual axes are not included in the physical axes.
PLC scan time
Tc
Cycle time of the PLC
Unit cycle
Tm = 1, 2, 3, 4, 6, or 8
This is the time required to execute a motion
task when there is only one motion task. Refer to
Calculation Method for Unit Cycle
Communications cycle
Ts = 1, 2, 3, or 4
Communications cycle of MECHATROLINK-II.
Refer to
Calculation Method for Communications
Cycle time extension time
No. of motion tasks
×
6
×
0.001 + No. of axes
×
8
×
0.001 + No. of allocated gen-
eral I/O words
×
0.001 + 0.6
The cycle time is extended by this amount of
time for each MC Unit mounted to the same
PLC.
Servo command response time
• W NS115
Td = 0.625
• W Series with built-in
MECHATROLINK-II
Td = 0.425
Time required before outputting current to the
motor after the Servo Driver receives a com-
mand via MECHATROLINK-II.
Operation startup time for automatic
operation
Min.: Tc + Tm + 2Ts + Td
Max.: 2Tc + 3Tm + 2Ts + Td
Time from enabling the start signal allocated to
an Input Unit of the PLC until outputting current
to the Servo Driver when there is only one
motion task and all axes are being operated.
Operation startup time for manual
operation
Min.: 0.7 + Tm + 2Ts + Td
Max.: Tc + 3Tm + 2Ts + Td
Time from turning ON the start bit (JOG bit) from
a ladder program in the PLC until outputting cur-
rent to the Servo Driver.
Offset per axis (interpolation, indepen-
dent operation)
0
• Time offset caused when interpolation is per-
formed with one motion task. There is no offset
between axes.
• Time offset caused when motion tasks with
one axis each are started simultaneously.
There is no offset between axes.
Status refresh offset per axis
0
Offset between refresh cycles between axes in
refreshing the status of the controlled axes
(present position, speed, input signals, etc.).
The status of all axes is always refreshed at the
same time, so there is no offset.
Minimum operation time
Tm
Minimum operation time required to stay in Pass
Mode.
The same as the Unit Cycle.
Minimum traverse reversal time
Tm
Minimum time required for reversal operation of
traverse command. The same as the Unit cycle.
External input response time (Unit
Built-in general input)
Tm or less
Time from accepting the Unit built-in general
input until it is reflected to input variables. It is
less than Unit cycle.
External input response time (Unit
Built-in deceleration stop input)
Min.: 2Ts + Tm + Td
Max.: 2Ts + 2Tm + Td
Time from receiving deceleration stop input until
current is output to the Servo Motor.
External input response time (CW/
CCW limit origin proximity input)
Min.: 4Ts + 2Tm + Td
Max.: 4Ts + 3Tm + Td
Time from when the Servo Driver detects the
input until current is output to the Servo Motor.
Содержание CS1W-MCH71 -
Страница 2: ...CS1W MCH71 CJ1W MCH71 Motion Control Unit Operation Manual Revised June 2008 ...
Страница 3: ...iv ...
Страница 29: ...xxx ...
Страница 33: ...xxxiv ...
Страница 35: ...xxxvi ...
Страница 39: ...xl ...
Страница 69: ...24 Performance Section 1 7 ...
Страница 99: ...54 Connecting MECHATROLINK Devices Section 3 5 ...
Страница 283: ...238 Saving Data Section 5 4 ...
Страница 417: ...372 Command Details Section 6 3 ...