![Omron CS1W-MCH71 - Скачать руководство пользователя страница 702](http://html1.mh-extra.com/html/omron/cs1w-mch71/cs1w-mch71_operation-manual_742367702.webp)
657
Error Log
Section 11-9
Error code
The error codes are classified into the CPU errors and MC Unit errors.
CPU Error Codes
Error
code
(Hex)
Error name
Detailed code
Cause
1st byte
2nd byte
0001
CPU WDT error
00
00
The watchdog timer alarm occurred on CPU
Unit.
Provide remedy following instructions in the
manual of the CPU Unit.
0002
CPU cyclic ser-
vice monitor error
Monitor time (ms)
Time out of the cyclic monitor time.
The followings are the possible causes:
• End refresh is prohibited on CPU Unit.
• The scan time of CPU Unit is too long.
Remedies:
Enable end refresh
Set the longer cyclic monitor time.
000E
CPU bus error
00
00
CPU Unit Bus error
0015
Fatal CPU error
00
00
Fatal error occurred on CPU Unit.
Check if MC Unit is mounted on the backplane
correctly. If the error persists even after the
checking and correction, CPU Unit or the back-
plane may be broken. Replace it as needed.
0016
Non-fatal CPU
error
00
00
Non-fatal error occurred on CPU Unit.
Provide remedy following instructions in the
manual of CPU Unit.
0108
Routing error
In a command:
When SNA < 80
Hex
D7:OFF
D6 to D0:SNA
SNA> = 80Hex
D7:OFF
D6 to D0:0
In a response:
When DNA<80Hex
D7:ON
D6 to D0:DNA
DNA> = 80Hex
D7:ON
D6 to D0:0
D7 to D0:SA1
D7 to D0:SNA
(SNA> = 80Hex)
D7 to D0:DA1
D7 to D0:DNA
(DNA> = 80Hex)
Transfer not possible because there is no Unit
for the specified unit number
Normally, this error does not occur. If it should
occur, report to OMRON.
010D
Routing error
Transfer not possible because the destination
address in the routing table has not been set.
Normally, this error does not occur. If it should
occur, report to OMRON.
010E
Routing error
Transfer not possible because of a routing table
error.
Normally, this error does not occur. If it should
occur, report to OMRON.
0118
Incorrect packet
error
An incorrect packet has been transferred.
Normally, this error does not occur. If it should
occur, report to OMRON.
0124
Routing error
Routing not possible because the maximum
frame length has been exceeded.
Normally, this error does not occur. If it should
occur, report to OMRON.
0601
Panic generated
Panic data
Set if trap processing has been executed.
Normally, this error does not occur. If it should
occur, report to OMRON.
Содержание CS1W-MCH71 -
Страница 2: ...CS1W MCH71 CJ1W MCH71 Motion Control Unit Operation Manual Revised June 2008 ...
Страница 3: ...iv ...
Страница 29: ...xxx ...
Страница 33: ...xxxiv ...
Страница 35: ...xxxvi ...
Страница 39: ...xl ...
Страница 69: ...24 Performance Section 1 7 ...
Страница 99: ...54 Connecting MECHATROLINK Devices Section 3 5 ...
Страница 283: ...238 Saving Data Section 5 4 ...
Страница 417: ...372 Command Details Section 6 3 ...