225
IOWR Instruction to Transfer Data
Section 5-2
Example 3) Write the servo parameters using IOWR instruction
• To write the servo parameters, the servo parameter axis has to be speci-
fied in advance. Write the axis No. in 6000h of IORD/IOWR control code
(address in the MC Unit).
• The setting value for the servo parameter axis specification is to be [Axis
No. - 1] as shown below:
• IORD/IOWR control addresses (address in MC Unit) corresponding to the
parameter Nos. of the servo driver (Pn000 to Pn8FF) are as shown below:
Procedure
1,2,3...
1.
Set the data in the data area of the transfer source.
2.
Specify the servo parameter axis.
3.
Transfer the parameter setting values for the number needed.
Axis No.
Setting value for specifying axis
1
0h
2
1h
3
2h
:
:
30
1Dh
31
1Eh
32
1Fh
Parameter No.
Address in MC Unit
Pn000
7000h
Pn001
7001h
Pn002
7002h
:
:
Pn8FD
78FDh
Pn8FE
78FEh
Pn8FF
78FFh