7
7.3
List of faults and warnings
7-675
Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
615
DM encoder limiting frequency exceeded
Cause
The speed actual value of the direct measuring system exceeds the
permissible encoder limiting frequency.
– Incorrect encoder
– P1007 does not coincide with the encoder pulse number
– Encoder defective
– Defective encoder cable or not correctly retained
– Encoder cable shield is not connected
– Defective control module
Remedy
– Enter correct encoder data/replace encoder
– Check encoder pulse number (P1007)
– Correctly retain encoder cable/replace
– Connect encoder cable shield
– Reduce speed setpoint input
– Replace control module
Acknowledgement RESET FAULT MEMORY
Stop response
parameterizable
616
DC link undervoltage
Cause
The DC link voltage has exceeded the permissible lower limit P1162.
Remedy
– Check whether the line supply voltage is available
– Check whether the pulsed resistor is overloaded
Acknowledgement RESET FAULT MEMORY
Stop response
parameterizable
617
DC link overvoltage
Cause
The DC link voltage has exceeded the permissible upper limit P1163.
Remedy
– Check whether the line supply voltage is available
– Reduce load duty cycle
– Check P1163
Acknowledgement RESET FAULT MEMORY
Stop response
parameterizable
680
Illegal motor code number
Cause
A motor code was entered in P1102 for which no data is available.
Remedy
Start-up again and enter the correct motor code number (P1102).
Acknowledgement POWER ON
Stop response
STOP II (SRM, SLM) STOP I (ARM)
7 Fault Handling/Diagnostics
01.99
04.05