background image

Installation, Operation &  
Application Guide

For more information on our complete 
range of American-made products – plus 
wiring diagrams, troubleshooting tips and 
more, visit us at 

www.icmcontrols.com

Installation of the ICM330 shall be performed by trained technicians only. Adhere to all local and 
national electric codes. 
Disconnect all power to the system before making any connections.

Caution!

• 

Line voltage:

 120, 208, 240, 277, and 480 VAC

• 

Control voltage:

 18-30 VAC

•  Current:

 4 amps maximum

• 

Frequency:

 50-60 Hz

• 

Operating temperature:

 -40ºF to +176ºF (-40°C to +75°C)

• 

Probes:

 

– Temperature: Thermistor, 10K ohm at 77°F (25°C) 
– Pressure: ICM380 (ordered separately)

• 

Heat pump override:

 24 VAC N.C. or N.O.

• 

Weight:

 12 ounces (341 grams)

 

Note:

 The 

ICM330

 should be applied to motors and equipment that have been designated by their 

respective manufacturers as capable of being speed controlled.

•  Mounting:

 

  –  Surface mount using (2) #8 screws
  –  It is recommended that the 

ICM330

 be mounted away from the condenser exhaust air in order to 

maintain lower operating temperatures

Specifications

ICM330

Head Pressure Control with 

Optional Heat Pump Override

Regulates head pressure via temperature or pressure input

Connections for ICM330 at 120/208/240/277 VAC

1.  Remove power from system.
2.  Field install a wire from 

Line 1

 wire to 

120/280 VAC

 terminal.

3.  Cut 

Line 2

 wire; affix motor side to 

Motor 2

 terminal and line side to 

Line 2

 terminal.

4.  Make 24 VAC, probe and HP connections.
5.  Verify wiring is correct.
6.  Power up system and check operation.

Field Installed Wire

1.  Remove power from system.
2.  Field install a wire from 

Line 1

 wire to 

480 VAC

 terminal.

3.  Cut 

Line 2

 wire; affix motor side to 

Motor 2

 terminal and line side to 

Line 2

 terminal.

4.  Make 24 VAC, probe and HP connections.
5.  Verify wiring is correct.
6.  Power up system and check operation.

Connections for ICM330 at 480 VAC

Field 
Installed 
Wire

Connections for Heat Pump System at 480 VAC

1. Remove power from system.
2. Field install a wire from 

Line 1

 wire to 

480 VAC

 terminal.

3. Cut 

Line 2

 wire; affix the common from the defrost 

board’s fan relay to the 

Motor 2

 terminal and the Line 

from the contactor to the 

Line 2

 terminal.

4. Make 24 VAC, probe and HP connections.
5. Verify wiring is correct.
6. Power up system and check operation.

Connections for Heat Pump System at 120/208/240/277 VAC

1. Remove power from system.
2. Field install a wire from 

LINE 1

 wire to 

120/280

 

VAC

 terminal.

3. Cut 

Line 2

 wire; affix the common from the defrost board’s 

fan relay to the 

Motor 2

 terminal and the Line from the 

contactor to the 

Line 2

 terminal.

4. Make 24 VAC, probe and HP connections.
5. Verify wiring is correct.
6. Power up system and check operation.

Example

1. Only one probe type can be used at a time, temperature OR pressure. 
2. A typical installation is shown in Appendix section. The temperature probe can 

be attached to the U-bend. Use the provided thermo-tape to secure the probe 
to the place of attachment. 

3. When using a pressure probe, install it on the discharge line transducer fitting.
4. A temperature or pressure probe is connected to ICM330 as shown in the 

respective wiring diagram below.

Installing and Connecting the Probe

Temperature Probe

BLUE  WHITE  GREEN

RED

BLACK

PRESSURE TRANSDUCER

Field Installed 

Wire

PSC 

Fan 

Motor

Run  

Capacitor

Fan 

Relay

COM

NC

Defrost Board

Field Installed 

Wire

PSC 

Fan 

Motor

Run  

Capacitor

Fan 

Relay

COM

NC

Defrost Board

1. 

For non-heat pump applications

, the heat pump select jumper must be in the 

Default

 (

N.O.

position, and the HP terminals must be left unconnected.

2. Set the Cutout Speed and the Hard Start Time to the appropriate positions for the type of motor you 

have (see below).

Connections for Air Conditioning Only

Reviews: