A
A.1
Parameter list
A-752
Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
0314
Activating software limit switch
Min
Standard
Max
Unit
Data type
Effective
0
0
1
–
Unsigned16
PrgE
1
Software limit switch active
0
Software limit switch inactive (e.g. necessary for a rotary axes)
Note:
With P0314=0, for a linear axis, the software limit switch monitoring remains active. Only the
limits are set to +–200000000.
0315
Minus software limit switch
Min
Standard
Max
Unit
Data type
Effective
–200000000
–200000000
200000000
MSR
Integer32
PrgE
... the position for the software limit switch is set to minus.
Note:
P0315 (minus software limit switch) < P0316 (plus software limit switch)
0316
Plus software limit switch
Min
Standard
Max
Unit
Data type
Effective
–200000000
200000000
200000000
MSR
Integer32
PrgE
... the position for the software limit switch is set to plus.
Note:
P0315 (minus software limit switch) < P0316 (plus software limit switch)
0318:8
Dynamic following error monitoring tolerance
Min
Standard
Max
Unit
Data type
Effective
0
1000
200000000
MSR
Unsigned32
immed.
... defines the maximum deviation between the measured and the calculated position actual
value before an error is output.
>= 1
The dynamic following error monitoring is active with this value
0
Monitoring is de-activated
Note: refer to the index entry ”Dynamic following error monitoring”
0320
Position monitoring time
Min
Standard
Max
Unit
Data type
Effective
0
1000
100000
ms
Floating Point
immed.
... defines the time after which the following error must be within the positioning window
(P0321).
Note: refer to the index entry ”Positioning monitoring”
0321
Positioning window
Min
Standard
Max
Unit
Data type
Effective
0
40
20000
MSR
Unsigned32
immed.
... defines the positioning window, within which the position actual value must be located after
the position monitoring time has expired (P0320).
>= 1
The position monitoring is active with this value
0
Monitoring is de-activated
Note: refer to the index entry ”Positioning monitoring”
0325
Standstill monitoring time
Min
Standard
Max
Unit
Data type
Effective
0
400
100000
ms
Floating Point
immed.
... defines the time after which the following error must be within the standstill window (P0326).
Note: refer to the index entry ”Standstill monitoring”
A Lists
01.99
! 611ue diff !
04.05