Induction motor operation with induction motor
4-143
Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
Note
For pure IM operation, a rotor position encoder is not necessarily
required. A fixed temperature must be selected in P1608, as in this
case, generally temperature sensing is not connected.
When IM operation is selected, only drive converter frequencies
(P1100) of 4 or 8 kHz are permissible.
Reference:
/PJU/
SIMODRIVE 611,
Configuration Manual, Drive Converters
Chapter ”Power modules”
The actual operating status of the drive is displayed in P0600 (oper-
ating display) (refer to Chapter 4.5).
When high–speed special motors are used, or other low leakage induc-
tion motors, a series reactor may be required to ensure stable oper-
ation of the current controller.
This reactor is taken into account in the current model using P1119.
Operating display
Series reactor
4 Commissioning