SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
The actual drive active power is displayed using this status word.
The active power is calculated from the speed actual value and the ac-
tual torque setpoint. Contrary to the torque and power limits, in this
case, the current limiting is not taken into account.
Pwirk
Data transfer format:
100
1 kW
Update rate at which this signal is provided:
Clock–cycle synchronous PROFIBUS–DP
––> n–set mode:
Position controller clock cycle (T
MAPC
) of the
master
––> pos mode: Position controller clock cycle (P1009)
non–clock–cycle synchronous PROFIBUS–DP
––> n–set mode:
Position controller clock cycle (P1009)
––> pos mode:
Interpolation clock cycle (P1010)
The drive torque is displayed using this status word.
Msoll
The normalization of Msoll is defined (from SW 4.1) using P0882 (eva-
luation, torque setpoint PROFIBUS).
actual torque setpoint for
synchronous motors:
Torque setpoint [Nm] = P1118
P1113
P0882
4000
hex
Msoll
Induction motors:
Torque setpoint [Nm] =
P0882
4000
hex
Msoll
60
P1130
1000
2
π
P1400
Note
The reference torque is displayed in P1725 (normalization, torque
setpoint).
The torque value is smoothed via P1252 (transition frequency, torque
setpoint smoothing).
Transfer format: 4000
Hex
= 16384
reference torque (in P1725)
Update rate at which this signal is provided:
Clock–cycle synchronous PROFIBUS–DP
––> generally:
DP clock cycle, sensed at instant in time T
i
non–clock–cycle synchronous PROFIBUS–DP
––> n–set mode:
Position controller clock cycle (P1009)
––> pos mode:
Interpolation clock cycle (P1010)
Status word Pwirk
Status word Msoll
Normalization of
Msoll (P0882)
5 Communications via PROFIBUS DP
08.99
02.02
04.05