List of faults and warnings
7-639
Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
108
Block number \%n available twice
Cause
There are several traversing blocks with the same block number in the
program memory. The block numbers must be unique over all travers-
ing blocks.
Remedy
Assign unique block numbers.
Acknowledgement RESET FAULT MEMORY
Stop response
STOP VI
109
External block change not requested in block \%n
Cause
External block change was not requested for a traversing block with
block step enable CONTINUE EXTERNAL and P0110 (configuration of
external block change) = 0.
Remedy
Remove the cause that the signal edge is missing at the input terminal
or for a PROFIBUS control signal STW1.13 or for the appropriate field-
bus signal.
Acknowledgement RESET FAULT MEMORY
Stop response
STOP V
110
Selected block number \%n does not exist
Cause
A block number was selected which is not available in the program
memory or has been suppressed.
Remedy
Select the existing block number.
Program the traversing block with the selected block number.
Acknowledgement RESET FAULT MEMORY
Stop response
STOP VI
111
GOTO in block number \n not permissible
Cause
The step command GOTO may not be programmed for this block number.
Remedy
Program another command.
Acknowledgement RESET FAULT MEMORY
Stop response
STOP VI
112
Activate traversing task and start referencing, hand-
wheel simultaneously
Cause
A positive signal edge was simultaneously detected for the input sig-
nals ”Activate traversing task” and ”Start referencing” and ”Activate
handwheel”.
At power-on or POWER-ON RESET, if both input signals have a ”1”
signal, then for both signals a 0/1 edge (positive edge) is simulta-
neously identified.
Remedy
Reset both input signals, and re-start the required function after the
fault has been acknowledged.
Acknowledgement RESET FAULT MEMORY
Stop response
STOP IV