7
7.3
List of faults and warnings
7-654
Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
184
Teach-in standard block not found
Cause
The specified teach-in standard block is not found.
Remedy
Generate the required standard block for the specified block number
Enter the correct block number.
Acknowledgement RESET FAULT MEMORY
Stop response
STOP IV
185
Positioning mode invalid
Cause
For the ”Spindle positioning” function, the positioning mode (P0087) is
not valid.
Remedy
Program traversing block positioning as absolute, absolute positive or
absolute negative.
Acknowledgement RESET FAULT MEMORY
Stop response
STOP II
186
Spindle cannot be referenced, supplementary info \%d
Cause
For the ”Spindle positioning” function, an error has occurred while posi-
tioning.
Supplementary info Significance
0
The distance between the last two zero marks was not correct.
1
For two revolutions a zero mark was no longer detected, which
was in a tolerance bandwidth of P0126.
Remedy
Check cable and connections.
Acknowledgement RESET FAULT MEMORY
Stop response
STOP II
7 Fault Handling/Diagnostics
01.99
04.05