1
1.4
”SIMODRIVE 611 universal E” control board
1-46
Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
1.4.3
Description of the terminals, interfaces and operator control ele-
ments
The board–specific terminals and interfaces are available, common for
both drive A and B.
Table 1-5
Overview of the board–specific terminals and interfaces
Terminals
Function
Type
1)
Technical data
No.
Desig-
nation
1)
Signaling terminal, start inhibit (X421)
AS1
X421
Signaling contact
Start inhibit
Feedback signal
NC
Connector type:
2–pin conn. strip
Max. cond. cross–sect.: 2.5 mm
2
Contact:
Floating NC contact
AS2
X421
Feedback signal
from terminal 663
Contact:
Floating NC contact
Contact load capability:
at 250 V
AC
max. 1 A
at 30 V
DC
max. 2 A
Relay, safe
start inhibit
AS2
AS1
T. 663
T. 663
Pulses not enabled (T. 663)
The gating pulses of the power
transistors are inhibited.
Pulses enabled (T. 663)
The gating pulses of the power
transistors are enabled.
Relay, safe
start inhibit
AS2
AS1
Terminals for supply and pulse enable (X431)
X431
Connector type:
5–pin conn. strip
Max. cond. cross–sect.: 1.5 mm
2
P24
X431.1
External power sup-
ply for digital outputs
(+24 V)
S
Voltage tolerance
(including ripple): 10 V to 30 V
Max. total current:
2.4 A
Note:
The external supply is required for the 4 digital out-
M24
X431.2
Reference for the
external supply
S
The external supply is required for the 4 digital out-
puts (O0.A, O1.A and O0.B, O1.B).
When dimensioning the external power supply, the
total current of all of the digital outputs must be
taken into account.
9
X431.3
Enable voltage
(+24 V)
S
Reference:
Terminal 19
Maximum current (for the total group):
500 mA
Note:
The enable voltage (terminal 9) can be used to supply
the enable signals (e.g. pulse enable) as 24 V auxil-
iary voltage.
1) NC: NC contact; S: Supply
Board–
specific terminals
and
interfaces
1 Product Overview
01.99
10.99