List of faults and warnings
7-678
Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
708
Axial deviations in current controller cycle
Cause
On a 2-axis module, the current controller cycle is different for both
axes.
Remedy
Check P1000 and set the input values the same for both drives.
Acknowledgement POWER ON
Stop response
STOP II (SRM, SLM) STOP I (ARM)
709
Axial deviations in speed controller cycle
Cause
On a 2-axis module, the speed controller cycle is different for both
axes.
Remedy
Check P1001 and set the input values the same for both drives.
Acknowledgement POWER ON
Stop response
STOP II (SRM, SLM) STOP I (ARM)
710
Axial deviations in position controller or interpolation
cycle
Cause
For a 2-axis module, the position controller clock cycle (P1009) or the
interpolation clock cycle (P1010) is different for the two axes.
Remedy
Check P1009/P1010 and set the input values for both drives the same.
Acknowledgement POWER ON
Stop response
STOP II (SRM, SLM) STOP I (ARM)
716
Invalid torque constant
Cause
The ratio between the rated torque and rated current (torque constant
[Nm/A]) in P1113 is incorrect (less than/equal to zero) or the ratio
P1113/P1112 is greater than 70.
Remedy
Enter the valid torque/current ratio for the motor used in P1113 or enter
a permissible ratio of P1113/P1112.
Third-party motor:
The torque constant should be determined from the motor data sheet.
Siemens motor:
The torque constant is defined by the motor code (P1102).
Acknowledgement POWER ON
Stop response
STOP II (SRM, SLM) STOP I (ARM)