7
7.3
List of faults and warnings
7-656
Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
190
Actual firmware does not support spindle positioning
Cause
This firmware does not support the spindle positioning function.
Remedy
Set parameter P0125 to 0
Acknowledgement POWER ON
Stop response
STOP II
191
Zero mark setting unsuccessful
Cause
It is not possible to set the internal zero mark, if
1st input signal ”Spindle positioning on” is set, or
2. Still no zero mark found.
Remedy
Maintain the following sequence:
1. Execute spindle positioning ––> zero mark found
2. Withdraw input signal ”spindle positioning on”
3. Set the internal zero mark (P0127=1).
Acknowledgement RESET FAULT MEMORY
Stop response
STOP II
192
Max. search velocity too high
Cause
The maximum search velocity for spindle positioning is greater than the
maximum motor speed.
Remedy
Reduce parameter P0133 or reduce the velocity in the traversing block.
Acknowledgement RESET FAULT MEMORY
Stop response
STOP II
193
Zero mark not found
Cause
The zero mark (encoder or equivalent zero mark, e.g. BERO) was not
found. Gearbox ratio (mechanical system) was not correctly parameter-
ized using parameter P0237/P0238.
Remedy
– Check the equivalent zero mark (BERO) function, if required, replace
the BERO
– Readjust the clearance when using BERO
– Check the cabling
– Correctly parameterize the gearbox ratio (mechanical system) using
parameter P0237/P0238
Acknowledgement RESET FAULT MEMORY
Stop response
STOP II
194
Spindle positioning is only possible with motor 1
Cause
Spindle positioning is only possible with motor 1.
Remedy
Activate motor data set 1 before the spindle positioning command.
Acknowledgement RESET FAULT MEMORY
Stop response
STOP II
7 Fault Handling/Diagnostics
01.99
04.05