Analog inputs
6-532
Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
The following parameters are available to parameterize the n
set
mode
using terminal 56.x/14.x and/or terminal 24.x/20.x:
Table 6-52
Parameters for the n
set
mode
Parameters
No.
Description
Min.
Stan-
dard
Max.
Units
Effec-
tive
0606
Voltage at terminals 56.x/14.x
–
–
–
V(pk)
RO
0611
Voltage at terminals 24.x/20.x
–
–
–
V(pk)
RO
... indicates the analog voltage presently available at this input terminal.
0608
Inversion, terminal 56.x/14.x
0
0
1
–
Imme-
diately
0613
Inversion terminal 24.x/20.x
0
0
1
–
Imme-
diately
An inversion internally inverts the sign of the analog setpoint at this terminal. The motor direc-
tion of rotation is reversed.
0
No inversion
1
Inversion
There is the following assignment between inversion, direction of rotation, and setpoint:
Without inversion, the motor rotates clockwise for a positive setpoint
With inversion, the motor rotates anti–clockwise for a positive setpoint
Definition of the direction of rotation:
When viewing the output shaft, the shaft rotates counter–clockwise
The motor direction of
rotation is counter–clockwise
When viewing the output shaft, the shaft rotates clockwise
The motor direction of rotation
is clockwise
0609
Smoothing time, terminal 56.x/14.x
(SRM, SLM)
(ARM)
0.0
0.0
3.0
1 000.0
ms
Imme-
diately
0614
Smoothing time, terminal 24.x/20.x
(SRM, SLM)
(ARM)
0.0
0.0
3.0
1 000.0
ms
Imme-
diately
This allows the output of the A/D converter to be smoothed using a PT
1
filter.
0610
Drift/offset correction terminal 56.x/14.x
–9 999.9
0.0
9 999.9
mV(pk)
Imme-
diately
0615
Drift/offset correction terminal 24.x/20.x
–9 999.9
0.0
9 999.9
mV(pk)
Imme-
diately
If the motor still continues to turn even with a speed setpoint of 0 V, and this is not desired, then
this parameter can be used to enter a voltage offset to adjust the analog input for zero output.