6
6.2
Positioning mode (P0700 = 3, from SW 2.1)
6-415
Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
Table 6-38
Parameters used to program traversing blocks, continued
No.
Effective
Units
Max.
Standard
Min.
Name
8
FIXED ENDSTOP (from SW 3.3)
The ”traverse to fixed endstop” function is activated using this command.
9
COUPLING_IN (from SW 3.3)
10
COUPLING_OUT (from SW 3.3)
Using these commands, the axis coupling that can be switched–in/out can be
switched–in/out in the ”positioning” mode.
Note:
The block change enable ”CONTINUE EXTERNAL” can be
parameterized in the traversing block ”COUPLING IN”. In the ”COUPLING OUT”
traversing block, a fault is output for ”CONTINUE EXTERNAL”.
0086:64
Command parame-
ters
0
1
65 535
–
PrgE
... specifies the additional information required for the following commands.
Command
Additional information
WAITING
Waiting time in ms
GOTO
block number
SET_O
1, 2, 3: Set direct output 1, 2 or 3 (both signals)
RESET_O
1, 2, 3: Reset, direct output 1, 2 or 3 (both signals)
FIXED ENDSTOP (from SW 3.3)
Clamping torque or clamping force
Rotary drive: 1 – 65 535 [0.01 Nm]
Linear drive: 1 – 65 535 [N]
Note:
The command–dependent required block information is listed in the Table 6-37.