Input/output terminals of the control board
6-524
Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
Table 6-49
List of output signals, continued
Operating
mode
Signal name, description
PROFIBUS bit
pos
n–set
Fct. No.
Direct output 1 via the traversing block
80
–
x
PosZsw.10
Direct output 2 via the traversing block
81
–
x
PosZsw.11
For output terminals:
If an output is parameterized with this function, then this output can be set or reset from the traversing
block using the SET_O or RESET_O command.
For PROFIBUS–DP:
The status signals can be set or reset from the traversing block using the SET_O or RESET_O com-
mand.
Note:
The following commands are used to set and reset output signals:
SET_O/RESET_O command and command parameter = 1 ––> set/reset direct output 1
SET_O/RESET_O command and command parameter = 2 ––> set/reset direct output 2
SET_O/RESET_O command and command parameter = 3 ––> set/reset both signals
Programming traversing blocks is described in Chapter 6.2.10.
Velocity limiting active
82
–
x
PosZsw.1
The output signal indicates whether the velocity is limited.
The limiting is, for example, active if the programmed velocity is greater than the maximum velocity
(P0102), taking into consideration the override.
1 signal
Velocity is limited
0 signal
Velocity is not limited
P0102 (max. velocity)
Programmed velocity
v
t
1 signal
0 signal
Velocity
limiting is active
Limiting
is not active
Velocity limiting active
Limiting
is not active
Note:
This signal is not output when jogging via velocity!
MDI active (from SW 7.1)
83
–
x
AktSatz.15
The output signal indicates whether the MDI function is operational.
1 signal
The MDI function is active.
0 signal
The MDI function is not active.
6 Description of the Functions
01.99
! 611ue diff !
08.01
02.03