7
7.3
List of faults and warnings
7-642
Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
122
Parameter \%u: value range limits violated
Cause
The value range limit of the parameter was violated when the dimen-
sion system was changed over from inches to millimeters.
Remedy
Place the parameter value within the value range.
Acknowledgement POWER ON
Stop response
STOP II (SRM, SLM) STOP I (ARM)
123
Linear encoder for the selected dimension system illegal
Cause
For a linear encoder, the dimension system was set to degrees.
Remedy
Change the dimension system setting (P0100).
Acknowledgement POWER ON
Stop response
STOP II (SRM, SLM) STOP I (ARM)
124
Referencing and jog simultaneously started
Cause
For the ”start referencing” and ”Jog 1” and ”Jog 2” input signals, a posi-
tive edge was simultaneously identified.
Remedy
Reset both input signals, and re-start the required function after the
fault has been acknowledged.
Acknowledgement RESET FAULT MEMORY
Stop response
STOP V
125
Falling edge of the reference cam not identified
Cause
When moving away from the reference cams, the traversing range limit
was reached, as the 1/0 edge of the reference cam was not identified.
Remedy
Check the ”reference cam” input signal and repeat the reference point
approach.
Acknowledgement RESET FAULT MEMORY
Stop response
STOP II (SRM, SLM) STOP I (ARM)
126
Block \%n: ABS_POS for rotary axis, is not possible
without modulo conversion
Cause
The ABS_POS positioning mode is only permitted for a rotary axis with
activated module conversion (P0241 = 1).
Remedy
Use the valid positioning mode for this axis type.
Acknowledgement RESET FAULT MEMORY
Stop response
STOP VI
7 Fault Handling/Diagnostics
01.99
04.05