6.11 Motor changeover for induction motors (from SW 2.4)
6-584
Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
The following input and output signals are used to select the motor data
set and the associated motor:
Input terminal with
Fct. No. 5
”Motor data set
changeover, 1st input”
Fct. No. 6
”Motor data set
changeover, 2nd input”
Output terminal with
Fct. No. 11
”Motor 1 selected”
Fct. No. 12
”Motor 2 selected”
Fct. No. 13
”Motor 3 selected”
Fct. No. 14
”Motor 4 selected”
SIMODRIVE
611
universal
Note:
Output terminals with Fct. Nos. 11...14 are only controlled, if P1249=0!
Fig. 6-78 Input/output signals: freely–parameterizable terminals
Status signal
”Actual motor, 1st signal”
ZSW2.9
”Actual motor, 2nd signal”
ZSW2.10
”Motor being changed over”
(from SW 3.3)
ZSW2.11
SIMODRIVE
611
universal
Control signal
”Motor data set
changeover, 1st input”
STW2.9
”Motor data set
changeover, 2nd input”
STW2.10
”Motor changed over”
STW2.11
Fig. 6-79 Input/output signals: PROFIBUS signals
Selecting the
motor data sets
and motors via
input/output
signals