6
6.5
Input/output terminals for the optional TERMINAL module
6-526
Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
6.5
Input/output terminals for the optional TERMINAL module
An optional TERMINAL module has 8 input and 8 output terminals,
which can be freely parameterized (refer to Chapter 1.3.3).
A terminal is assigned any function by entering the function number
corresponding to the required function into the parameter assigned to
the terminal.
Notice
The terminals may only be parameterized when the drive pulses are
canceled.
The following assignment exists between the input/output terminals,
drives and parameters:
Table 6-50
Terminals and parameters for the optional TERMINAL module
Terminals
Parameters
Drive A/B
No.
Name
Min.
Stan-
dard
Max.
Units
Effec-
tive
Input terminals
I4
X422.1
0664
Function, input terminal I4
0
60
82
–
Immed.
I5
X422.2
0665
Function, input terminal I5
0
59
82
–
Immed.
I6
X422.3
0666
Function, input terminal I6
0
58
82
–
Immed.
I7
X422.4
0667
Function, input terminal I7
0
50
82
–
Immed.
I8
X422.5
0668
Function, input terminal I8
0
51
82
–
Immed.
I9
X422.6
0669
Function, input terminal I9
0
52
82
–
Immed.
I10
X422.7
0670
Function, input terminal I10
0
53
82
–
Immed.
I11
X422.8
0671
Function, input terminal I11
0
54
82
–
Immed.
Output terminals
O4
X432.1
0684
Signaling function
output terminal O4
0
72
82
–
Immed.
O5
X432.2
0685
Signaling function
output terminal O5
0
60
82
–
Immed.
O6
X432.3
0686
Signaling function
output terminal O6
0
62
82
–
Immed.
O7
X432.4
0687
Signaling function
output terminal O7
0
50
82
–
Immed.
O8
X432.5
0688
Signaling function
output terminal O8
0
51
82
–
Immed.
Description
Overview of the
terminals and
parameters
6 Description of the Functions
01.99
! not 611ue !
02.02