SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
1051
IM ref. mark clearance for distance-coded rotary enc.
(–> 4.1)
Min
Standard
Max
Unit
Data type
Effective
0
20000
4294967295
mDegree
Unsigned32
PO
...specifies the basic clearance between two fixed reference marks. If the closed-loop identifies
that the distance between each second reference mark is different and is therefore incorrect,
the axis remains stationary. Fault 508 (zero mark monitoring, motor measuring system) is sig-
naled.
Note:
IM ––> Indirect measuring system (motor encoder)
This monitoring is only activated, if P1051/1000*P1005/360 can either be divided by 16 or by
10.
1052
DM reference mark distance for distance-coded scales (–> 4.1)
Min
Standard
Max
Unit
Data type
Effective
0
20000
4294967295
µ
m
Unsigned32
PO
...specifies the basic clearance between two fixed reference marks. If the closed-loop identifies
that the distance between each second reference mark is different and is therefore incorrect,
the axis remains stationary. Fault 514 (zero mark monitoring, direct measuring system) is sig-
naled.
Note:
DM ––> Direct measuring system
This monitoring is only activated, if P1052/P1034*1000 can either be divided by 16 or by 10.
1053
DM ref. mark distance for distance-coded rotary enc.
(–> 4.1)
Min
Standard
Max
Unit
Data type
Effective
0
20000
4294967295
mDegree
Unsigned32
PO
... specifies the basic distance between two fixed reference marks. If the control recognizes that
the distance between each second reference mark differs, and is therefore incorrect, the axis
remains stationary. Fault 514 (zero mark monitoring, direct measuring system) is signaled.
Note:
This monitoring is only activated, if P1053/1000*P1007/360 can either be divided by 16 or by
10.
1054
IM difference for distance-coded encoders
(–> 8.3)
Min
Standard
Max
Unit
Data type
Effective
0
20
500000
µ
m
Unsigned32
PO
(SLM)
0
20
450000
mDegree
Unsigned32
PO
(SRM ARM)
... specifies the distance between two reference marks for distance-coded encoders, indirect
measuring system (motor measuring system).
1055
DM difference for distance-coded encoders
(–> 8.3)
Min
Standard
Max
Unit
Data type
Effective
0
20
500000
µ
m
Unsigned32
PO
(SLM)
0
20
450000
mDegree
Unsigned32
PO
(SRM ARM)
... specifies the distance between two reference marks for distance-coded encoders, direct
measuring system.