Settings at the PROFIBUS DP master
5-282
Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
If this is not possible, then the appropriate information must be derived
for the ”DP slave 611U” from the GSD file.
Reader’s note
Information on the PROFIBUS–DP master settings should be taken
from the literature of the master used.
Configuring defines the data, which the master transfers to the ”DP sla-
ves” at every bus run–up via the parameterizing telegram and the confi-
guration telegram.
Configuring can be realized in the following ways:
1. Using the GSD ”SIEM808F.GSD” or ”SI02808F.GSD”
2. Using the ”Slave Object Manager (Drive ES Slave–OM)”,
which is included in the following products:
Product
Order No. (MLFB):
Drive ES Basic V5.1 SP2
6SW1700–5JA00–1AA0 (single license)
6SW1700–5JA00–1AA1 (company license)
6SW1700–5JA00–1AA4 (upgrade)
Drive ES SIMATIC V5.2
6SW1700–5JC00–2AA0
6SW1700–5JC00–2AA4 (upgrade)
The products, require as basis, the basic SIMATIC–STEP 7 soft-
ware.
Compared to the GSD file, Drive ES offers a higher degree of user
friendliness regarding the telegram structure and clock cycle–synchro-
nous operation.
Slave–to–slave communications does not function without Drive ES.
The following is valid from SW 3.1:
The parameterizing and configuration data, received from the ”DP
slave 611U” are displayed in the following parameters:
P1783:64
received PROFIBUS parameterizing data
P1784:64
received PROFIBUS configuration data
Engineering
5 Communications via PROFIBUS DP
08.99
08.02