7
7.4
Commissioning functions
7-724
Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
The assignment between the test sockets and parameters is as fol-
lows:
Table 7-7
Overview of the test sockets
Test sockets
Parameters
No.
Name
Min.
Stan-
dard
Max.
Unit
s
Effec-
tive
1820
Signal number, test socket 1
0
8
530
–
Imme-
diately
... defines which signal is output via the DAU (D/A converter).
The signal number from the signal selection list must be entered for ana-
log output (refer to Chapter 6.7 under Table 6-56).
1821
Shift factor, test socket 1
0
6
47
–
Imme-
diately
Speed actual
value, motor
drive A
(standard)
... defines the shift factor, with which the output signal is manipulated.
Only an 8 bit output window can be output from a 24/48 bit signal due to
the 8–bit resolution. The shift factor can be used to define which eight of
the 24/38 bits are located in the output window and should be output.
(standard)
1822
Offset, test socket 1
–128
0
127
–
Imme-
diately
M
DAU1
DAU2
X34
... specifies the offset, which is added to the 8–bit output signal.
The signal to be output is shifted by 5/256 V (19.5 mV) by changing the
offset by 1 digit.
P1822 = –128
0 V, P1822 = 0
+2.5 V, P1822 = 127
+5V
M
DAU2
1826
Status, test socket 1
0
1
1
–
Imme-
diately
5 V
2.5 V
0 V of the
measuring
signal
0 V
... defines the status of the test socket for this drive.
= 0
Test socket is inactive
= 1
Test socket is active
As always only one drive can output one value at a test socket, when
changing the parameter in one drive, the parameter in the other drive is
automatically adapted.
Note:
For a 2–axis module, the test sockets are preset as follows after the first
start–up:
Drive A
Drive B
Test socket 1
active (P1826 = 1)
inactive (P1826 = 0)
Test socket 2
inactive (P1836 = 0)
active (P1836 = 1)
1830
Signal number, test socket 2
0
14
530
–
Imme-
diately
DAU1
X34
Description, refer to that for P1820.
DAU1
X34
1831
Shift factor, test socket 2
0
12
47
–
Imme-
diately
M
DAU2
Description, refer to that for P1821.
M
DAU2
1832
Offset, test socket 2
–128
0
127
–
Imme-
diately
Active power
drive B
Description, refer to that for P1822.
Active power
drive B
(as standard)
1836
Status, test socket 2
0
1
1
–
Imme-
diately
Description, refer to that for P1826.
Parameter
overview
7 Fault Handling/Diagnostics
01.99
02.02