SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
0969
Current time difference
Min
Standard
Max
Unit
Data type
Effective
0
0
0
ms
Unsigned32
immed.
... contains the relative system time since the last time that the drive was powered-up or the last
reset of the parameter or since the last counter overflow.
Note:
This parameter can only be read and reset, i.e. only a value of 0 can be written into it.
0972
Request POWER-ON RESET
(–> 3.3)
Min
Standard
Max
Unit
Data type
Effective
0
0
2
–
Unsigned16
immed.
... a POWER-ON RESET can be requested on the control board.
0
Output status
1
Request POWER-ON RESET
2
Request preparation for POWER-ON RESET
The DP master can check as follows, whether the power-on reset was executed:
– write 2 into P0972 and read-back the value
– write 1 into P0972 ––> POWER-ON RESET is requested
Read P0972 after communications have been established:
P0972 = 0? ––> the POWER-ON RESET was executed
P0972 = 2? ––> the POWER-ON RESET was not executed
Note:
After P0972=1, the link between the drive and SimoComU is interrupted with the following mes-
sage: ”Reading from the interface was interrupted due to time overflow”. The link is re-estab-
lished when SimoCom U is re-started.