Commissioning using the display and operator unit
4-128
Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
4.4
Commissioning using the display and operator unit
START
Power–up the unit (power ON)
Is the ”E– ...”? displayed flashing or
is the display inactive?
Remove the cause!
(refer to Chapter 7)
Is
”_ _ _ r u n”
displayed?
Connect–up the unit
Check the connections (refer to Chap. 2.3.1)
De–energize terminal 663 (pulses are then
not enabled)
Request
new
commissioning?
no
Is a
A1106
1)
or b1106
1)
displayed?
no
yes
yes
yes
no
yes
no
Remove write protection (P0651 = 4)
Establish the boot state (P0659 = 0)
Start to write into the FEPROM
(P0652 = 1) and then wait until the write
operation has been completed (P0652
= 0)
Execute a HW POWER–ON RESET or
POWER OFF
ON
Are both
drives
configured?
4)
no
yes
Press the + and – keys simultaneously (up to b0659)
Press the – key
up to b1106 in the display
Execute the hardware configuration
1. Axxxx, bxxxx: Parameters, drive A, B
2. Only set, if there is no automatic
power module identification available
(refer to Chapter 4.6)
3. The parameter value is changed using these keys
4. If drive B is not used, then b0700 = 0 (drive B inactive) and b0659 = 0 –> 1 (boot)
5. Set the PROFIBUS node address ––> refer to Chapter 5.7.2
3
Continue on the
next page
End
(cyclic
operation)
Establish the boot state
Oper. control
Display Description
A1106 Power module code No.
2)
Key P (+/–)
3)
Set the code (refer to Chapter A.2)
Key P, +
A1102 Motor code number
Key P (+/–)
3)
Set the code (refer to Chapter A.3)
Key P, +
A1006 Encoder code number
Key P (+/–)
3)
Set the code (refer to Chapter A.4)
Key P, +
A0700 Operating mode
Key P (+/–)
3)
Set the BM (refer to Chapter 4.6)
Key P, +
A0659 Boot
5)
Key P, +, P
Boot (P0659 = 0 –> 1)
Key P
A0659 or b0659 is displayed
3
1
Already
commissioned?
Fig. 4-3
Commissioning using the display and operator unit (Part 1 of 3)
4 Commissioning