Input/output terminals of the control board
6-514
Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
Table 6-49
List of output signals, continued
Operating
mode
Signal name, description
PROFIBUS bit
pos
n–set
Fct. No.
No OFF 3 present/OFF 3 present
–
x
x
ZSW1.5
1 signal
No OFF 3 present
0 signal
OFF 3 present
Power–on inhibit/no power–on inhibit
–
x
x
ZSW1.6
1 signal
Power–on inhibit
It is only possible to power–up the drive again using OFF 1 and then ON (STW1.0) (or
withdrawing terminal 65.x).
0 signal
No power–on inhibit
Note:
The ”power–on inhibit” function can be disabled via P1012.12.
No following error/following error
58
–
x
ZSW1.8
When the axis is traversed, closed–loop position controlled, using a model, the theoretically permissible
following error is calculated from the instantaneous traversing velocity and the selected Kv factor.
A following error window can be defined using P0318, which defines the permissible relative deviation
from this calculated value.
This output signal specifies whether the actual following error is within the following error window, defined
using P0318.
1 signal
No following error
The actual following error is within the defined following error window.
0 signal
Following error
The actual following error of the axis is outside the defined following error window.
Note:
Refer under the index entry ”Following error monitoring”.
Spindle position reached (from SW 5.1)
59
x
–
MeldW.15
This signal displays as to whether the target position has been reached.
1 signal
The spindle has reached the target position within the tolerance window (P0134).
0 signal
The spindle has not reached the target position or alarms 131, 134 and 135 have oc-
curred.
Note:
The ”spindle positioning” function is described in Chapter 6.15 (from SW 5.1).