1
1.3
”SIMODRIVE 611 universal” control board
1-41
Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
The ”SIMODRIVE 611 universal” control board can be
connected and operated as DP slave on the PROFIBUS–DP fieldbus
when this optional module is used.
X423
Two–color LED for diagnostics
For screws:
Tighten (due to the shield contact)
Max. torque = 0.8 Nm
Fig. 1-8
Optional PROFIBUS–DP module
Table 1-3
Which optional modules are available?
Designation
Order No. (MLFB)
Features
PROFIBUS–DP1
(can no longer be
used from SW
4.1)
6SN1114–0NB00–0AA0
PROFIBUS–ASIC SPC3
Cyclic data transfer (PKW and PZD section) possible
PROFIBUS–DP2
6SN1114–0NB00–0AA1
PROFIBUS–ASIC DPC31 without PLL
For control boards SW 3.1, this module can replace
the optional PROFIBUS–DP1 module
Features that
PROFIBUS–DP2 and DP3 have in common
Prerequisites:
Control board from SW 3.1 is required
Cyclic data transfer (PKW and PZD section) possible
FW module can be updated using SimoCom U
Non–cyclic data transfer (DP/V1)
”SimoCom U via PROFIBUS” possible
PROFIBUS–DP3
6SN1114–0NB01–0AA0
PROFIBUS–ASIC DPC31 with PLL
”Motion Control with PROFIBUS–DP” function (clock–
synchronous PROFIBUS operation) is possible
Optional
PROFIBUS–DP
module
1 Product Overview
01.99
! 611ue diff !
08.01