5
5.6
Net data (PKW and PZD area)
5-241
Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
Table 5-20
Status word PosZsw for positioning
Cam switching signal 1
Cam switching signal 2
ZSW
1
Akt
Satz
Pos
Zsw
Direct output 1 via the traversing block
Direct output 2 via the traversing block
Fixed end stop reached (from SW 3.3)
Fixed endstop clamp. torque reached (from SW 3.3)
Teach–in executed (from SW 4.1)
Traverse to fixed end stop active (from SW 3.3)
Bit
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Axis moves backwards
Tracking mode active
Setpoint static
Axis moves forwards
Minus software limit switch actuated
Plus software limit switch actuated
In synchronism (from SW 3.3)
Velocity limiting active
Note:
From the perspective of SIMODRIVE 611 universal, status signals are output signals and are described
in Chapter 6.4.6.
Also refer in the index under ”Output signal, digital ...”).
The actual DC link voltage in the drive is displayed using this status
word.
UZK1
Data transfer format: hexadecimal, non–normalized
e.g.: 258
hex
= 600
dec
= 600 V
The reading of the status word UZK1 should be configured in the stan-
dard telegram (P0922 = 0; refer to Chapter 5.6.5).
Status word
PosZsw
(pos mode)
Status word
UDClink1
(from SW 8.3)
5 Communications via PROFIBUS DP
08.99
07.01
08.01
04.05