7
7.3
List of faults and warnings
7-694
Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
790
Illegal operating mode. Supplementary info: \%u
Cause
The selected operating mode (P0700) is not permitted for this module
or axis.
Supplementary info = 0x1:
Operating mode ==0 selected on the 1st axis
Supplementary info = 0x2:
”Positioing” operating mode selected for the Nset control module
Supplementary info = 0x3:
Operating mode is not possible with this firmware release
Supplementary info =
”External position reference value” operating mode no longer possible.
Remedy
For supplementary info 1:
Select valid operating mode (P0700 > 0)
For supplementary info 2:
Select Nset operating mode or use a positioning module.
For supplementary info 3:
Use a firmware release which supports this operating mode.
For supplementary info 4:
Select ”Positioning” operating mode.
Acknowledgement POWER ON
Stop response
STOP I
791
TTL encoder interface incorrectly parameterized
Cause
The TTL encoder interface may only be parameterized as follows for
this particular hardware version:
Drive A: P0890 = 0 or 4, 0: Interface inactive, 4: TTL encoder input
Drive B: P0890 = 0
Remedy
Set P0890 to permissible value.
Acknowledgement POWER ON
Stop response
STOP II (SRM, SLM) STOP I (ARM)
7 Fault Handling/Diagnostics
01.99
04.05