6
6.2
Positioning mode (P0700 = 3, from SW 2.1)
6-424
Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
A traversing block can be interrupted using the ”OC reject/traversing
task” control signal.
Features:
A block, interrupted with ”reject traversing task” can no longer be
continued.
A ”delete distance to go” is executed.
It is also possible for a block with intermediate stop.
Activate
traversing
task
Setpoint
acknowledge
Reference
position
reached
Drive at
standstill
1
2
3
OC/reject
traversing task
4
OC/
intermediate stop
Control signal
Control signal
Control signal
Status signal
Status signal
Status signal
IPO clock
cycles
1
Selecting and starting the traversing block
2
Interrupting the traversing block using ”reject traversing task”
––>
”operating condition/reject traversing task” is reset
––>
”setpoint acknowledgement” is reset
––>
the axis is braked down to standstill with the maximum deceleration and ”drive stationary”
signaled if the speed limit for standstill is fallen below.
”Reference position reached” is not set.
3
Selecting and starting an additional (or the same) traversing block
4
End of positioning
Fig. 6-27 Characteristics when aborting a traversing block
Reject traversing
task
6 Description of the Functions
01.99