A
A.1
Parameter list
A-828
Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
1256:8
Ramp-function generator ramp-up time
(–> 2.4)
Min
Standard
Max
Unit
Data type
Effective
0.0
2.0
600.0
s
Floating Point
immed. (ARM)
0.0
0.0
600.0
s
Floating Point
immed. (SRM SLM)
During ramp-up, the setpoint is increased from zero to the maximum permissible actual speed.
Note:
Max. permissible actual speed for synchronous motors: Minimum from 1.1 (1.05 from SW 7.1
with ”SIMODRIVE 611 universal HR”, resolver) x P1400 and P1147
Max. permissible actual speed for induction motors: Minimum from P1146 and P1147
Max. permissible actual speed for linear motors: From P1147
refer to the index entry ”Ramp-function generator”.
1257:8
Ramp-function generator ramp-down time
(–> 2.4)
Min
Standard
Max
Unit
Data type
Effective
0.0
2.0
600.0
s
Floating Point
immed. (ARM)
0.0
0.0
600.0
s
Floating Point
immed. (SRM SLM)
During ramp-down, the setpoint is reduced from the maximum permissible actual speed to zero.
Note:
Max. permissible actual speed for synchronous motors: Minimum from 1.1 (1.05 from SW 7.1
with ”SIMODRIVE 611 universal HR”, resolver) x P1400 and P1147
Max. permissible actual speed for induction motors: Minimum from P1146 and P1147
Max. permissible actual speed for linear motors: From P1147
refer to the index entry ”Ramp-function generator”.
1259
Torque/power reduction mot./gen. (ARM SRM)
(–> 3.7)
Force/power reduction mot./gen. (SLM)
Min
Standard
Max
Unit
Data type
Effective
0
0
3
Hex
Unsigned16
immed.
... defines if the torque/power de-rating or force/power de-rating depends on whether the drive
is motoring/generating.
Bit 0
Torque/power reduction, only when motoring
Bit 0 = 1
Reduction is only effective when motoring
Bit 0 = 0
Reduction is effective when motoring and regenerating
Bit 1
Motoring/regenerating limiting dependent on Nset
Bit 1 = 1
The torque limits when motoring are used if the product of torque and speed
setpoint is positive and the speed setpoint is not equal to 0
Bit 1 = 0
The torque limits when motoring are used if the product of torque and speed
actual value is positive or the absolute speed actual value is less than 10 RPM
P1259 valid for input via PROFIBUS and analog input.
Note: refer to the index entry ”Torque/power reduction”
1260
i2t limiting, limit current, power section S6
(–> 3.1)
Min
Standard
Max
Unit
Data type
Effective
25.0
100.0
100.0
%
Floating Point
immed.
... for the i2t power section limiting, it defines the limiting characteristic referred to i-S6.
Note:
I-S6 = P1109 (limiting power section current S6) x P1099 (limiting factor, power section cur-
rents)
refer to the index entry ”i2t power section limiting”
A Lists
01.99
! 611ue diff !