A
A.2
Power module list
A-856
Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
A.2
Power module list
A power module is defined by its Order No. (MLFB) and internally by its
code number.
Table A-1
Power module Order No. and code
Order No.
(MLFB)
Power mod-
ule code
No. of
axes
Current rating
(MLFB)
ule code
axes
Tran–
sistor
current
Motor
1)
1FT6, 1FK6,
1FNx
Motor
1)
1PHx,
1FE1 (from SW 3.1)
P1106
[A(pk)]
P1107
I
n
/I
max
[A(rms)]
P1111/P1108
I
n
/I
S6
/I
max
[A(rms)]
P1111/P1109/P1108
6SN112x–1Ax0x–0HAx
1
1/2
8
3/6
3/3/3
6SN112x–1Ax0x–0AAx
2
1/2
15
5/10
5/5/8
6SN112x–1Ax0x–0BAx
4
1/2
25
9/18
8/10/16
6SN112x–1Ax0x–0CAx
6
1/2
50
18/36
24/32/32
6SN112x–1Ax0x–0DAx
7
1
80
28/56
30/40/51
6SN112x–1Ax0x–0LAx
13
2)
1
108
42/64
45/60/76
6SN112x–1Ax0x–0GAx
8
2)
1
120
42/64
45/60/76
6SN112x–1Ax0x–0EAx
9
1
160
56/112
60/80/102
6SN112x–1Ax0x–0FAx
10
1
200
70/140
85/110/127
6SN112x–1Ax0x–0JAx
11
2)
1
300
100/100
120/150/193
6SN112x–1Ax0x–0KAx
12
1
400
140/210
200/250/257
Note:
rms:
rms value
pk:
Peak value
x:
Space retainer for the Order No.
I
n
:
Continuous current
I
S6
:
Current for max. 4 min. for S6 load duty cycle
I
max
:
Peak current
1)
At higher pulse frequencies (P1100) I
n
, I
max
and I
S6
must be reduced to protect the power
module.
The following applies before SW 2.4:
The display using P1108, P1109 and P1111 depends on the pulse frequency.
The reduction factor is already calculated into this parameter.
The displayed values only correspond to the values in the table for the standard setting of the
pulse frequency (P1100).
The following applies from SW 2.4:
The display using P1108, P1109 and P1111 corresponds to the values in this table.
The limiting factor is displayed in P1099 (limiting factor, power module currents).
Example:
P1111 = 9 A, P1099 = 80 % ––> reduced rated current I
n
= 9 A
80 % = 7.2 A
2)
from SW 8.2 onwards (only for PE spindles)
Power module
Order No. and
code
A Lists
01.99
05.00