Commissioning functions
7-716
Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
The following parameters are used to parameterize the function gene-
rator:
Table 7-6
Parameters for the function generator
Parameters
No.
Description
Min.
Stan-
dard
Max.
Units
Effective
1800
Function generator control
–40
0
2
–
Immedi-
ately
... starts, exits the function generator and if a fault/error is present, displays the reason.
= 2
Synchronous start of the function generator (from SW 8.1)
= 1
Starts the function generator. The FG is again terminated with P1800 = 1
0.
= 0
Function generator is inactive
= –1
Commissioning–function was started; but was possibly already running on another
drive
= –2
Inadmissible mode or the mode was changed while the FG was active
= –4
The period is 0 or too high
= –6
The absolute amplitude is too high
= –7
The offset lies outside the permitted range
= –8
The limit is greater than permitted
= –9
Incorrect waveform or the waveform was changed while the FG was active
= –10
The pulse width is negative or greater than the period
= –11
The bandwidth is less than 1 Hz or greater than the maximum possible bandwidth
(for a sampling time of 0.125 ms, the maximum possible bandwidth is 4000 Hz)
= –15
The 2nd amplitude for the ”staircase” waveform is too high
= –16
The commissioning function was not started or was aborted due to an active inter-
nal regenerative stop
= –17
The commissioning function was not started or was aborted due to the missing
pulse enable
= –18
The commissioning function was not started or was aborted due to the missing
speed controller enable
= –19
The commissioning function was not started or was aborted due to the missing
”speed controlled mode” enable
= –20
The commissioning function was not started or was aborted due to a missing ramp–
function generator enable signal
= –21
The commissioning function was not started due to a traversing axis (e.g. active
traversing block)
=–23
The commissioning function was canceled because the synchronous start enable
was withdrawn
Parameter
overview
7 Fault Handling/Diagnostics