1
1.4
”SIMODRIVE 611 universal E” control board
1-50
Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
Table 1-6
Overview of the drive–specific terminals, continued
Terminals
Technical data
Type
1)
Function
Drive A
Technical data
Type
1)
Function
Drive B
No.
Technical data
Type
1)
Function
Desig-
nation
No.
Desig-
nation
O0.A
X453.9
O0.B
X454.9
Digital output 0
2)
DO
Rated current per output:
500 mA
Max. current per output:
600 mA
Voltage drop, typical:
250 mV at 500 mA
Short–circuit proof
O1.A
X453.10
O1.B
X454.10
Digital output 1
2)
DO
Short–circuit proof
Note:
Parameterization of the output termi-
nals as well as the standard assign-
ment is described in Chapter 6.4.5.
Note:
The power switched via these outputs is supplied via terminals P24/M24 (X431). This must be
taken into account when dimensioning the external supply.
The digital outputs only ”function” if an external power supply is available (+24 V, T. P24/M24).
1) DO: Digital output
2) Can be freely parameterized
The digital outputs are updated in the interpolation clock cycle (P1010). This is supplemented by a
hardware–related delay time of approx. 200
µ
s.
1 Product Overview
01.99
10.99
! not 611u !