A
A.1
Parameter list
A-772
Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
0701
Actual operating mode
Min
Standard
Max
Unit
Data type
Effective
–
–
–
–
Unsigned16
RO
0
Drive inactive (only drive B)
1
Speed/torque setpoint
– Closed-loop speed controlled operation (n-set operation)
– Open-loop torque controlled mode
(M setpoint operation)
– Torque reduction (M reduction)
2
External position reference value (from SW 3.3)
No longer available from SW 4.1.
3
Positioning (from SW 2.1)
0730:700 Saved parameters
(–> 6.1)
Min
Standard
Max
Unit
Data type
Effective
–
–
–
–
Unsigned16
RO
...includes all of the parameters taken into account when saving the drive configuration (save
parameter in a file).
The following steps are necessary for a series start-up without using the SimoCom U start-up
tool:
1. Signal the motor type (write into P1102 = motor code)
2. Writing 4 into P0659 (drive carries-out defaults)
3. Write into all of the parameters listed in parameter P0731
4. Write 2 into P0659 (pre-assign motor/ LT data, calculate controller data)
5. Write into all parameters listed in parameter P0730 (minus the parameters listed in P0731)
0731:250 Parameters required before start-up
(–> 6.1)
Min
Standard
Max
Unit
Data type
Effective
–
–
–
–
Unsigned16
RO
...contains all parameters which must be written into before commissioning.
The following steps are necessary for a series start-up without using the SimoCom U start-up
tool:
1. Signal the motor type (write into P1102 = motor code)
2. Writing 4 into P0659 (drive carries-out defaults)
3. Write into all of the parameters listed in parameter P0731
4. Write 2 into P0659 (pre-assign motor/ LT data, calculate controller data)
5. Write into all parameters listed in parameter P0730 (minus the parameters listed in P0731)
A Lists
01.99
! 611ue diff !