SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
773
Not permissible to active analog input
Cause
For this particular hardware version, it is not permissible to activate the
analog input.
Remedy
– Set P0607 to 0 and P0612 to 0 or
– Use the ”SIMODRIVE 611 universal” control module.
Acknowledgement POWER ON
Stop response
STOP II (SRM, SLM) STOP I (ARM)
774
Induction motor oper.: changeover speed motor \%d
not permissible
Cause
For mixed operation (with/without encoder) P1465 > 0, only closed-loop
controlled induction motor operation is permissible (P1466 <= P1465).
Remedy
Eliminate error by selecting pure induction motor operation (P1465 = 0)
or by canceling induction motor open-loop controlled operation (P1465
> P1466).
Acknowledgement RESET FAULT MEMORY
Stop response
STOP II (SRM, SLM) STOP I (ARM)
775
SSI encoder incorrectly parameterized. Supplementary
info \%u
Cause
Incorrect parameterization of the SSI absolute value encoder.
Supplementary info = 0x1, 0x11 (indirect, direct measuring system):
––> The single-turn resolution cannot be 0.
Supplementary info = 0x2, 0x12 (indirect, direct measuring system):
––> The number of parameterized bits is greater than the telegram
length.
Supplementary info = 0x3, 0x13 (indirect, direct measuring system):
––> For linear encoders, it is not possible to have multi-turn resolution.
Remedy
For supplementary info 1 or 11:
Check P1022 and P1032
For supplementary info 2 or 12:
Check P1021, P1022, P1027.12 and P1027.14 with respect to P1028
and check P1031, P1032, P1037.12 and P1037.14 with respect to
P1041
For supplementary info 3 or 13:
Check P1021 and P1031
Acknowledgement POWER ON
Stop response
STOP I
776
TTL encoder not possible for older basic module
Cause
For an old basic module, which does not support TTL encoders, a TTL
encoder was selected as motor measuring system.
Remedy
Use a new basic module or incremental measuring system with sin/cos
1 Vpp.
Acknowledgement POWER ON
Stop response
STOP I