Parameter list
A-786
Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
0918
PROFIBUS node address
Min
Standard
Max
Unit
Data type
Effective
0
0
126
–
Unsigned16
PO
... specifies the address of the drive as DP slave on PROFIBUS.
Note:
There is only one node address for the control module, although it is designed for two drives.
When changing the parameters in one drive, the parameters in the other drive are automatically
modified.
Every node connected to PROFIBUS must have a unique address.
0922
PROFIBUS frame selection
(–> 3.1)
Min
Standard
Max
Unit
Data type
Effective
0
101
110
–
Unsigned16
PO
... serves for setting the free configurability or for selecting a standard frame.
0
The frame can be freely configured (see P0915:17, P0916:17)
1
standard frame 1, n-set interface 16 bits
2
Standard frame 2, n-set interface 32 bits without encoder
3
Standard telegram 3, n set interface 32 bit with encoder 1
4
Standard telegram 4, n-set interface 32 bit with encoder 1 and encoder 2 (from SW 3.3)
5
Standard telegram 5, n set interface 32 bit with DSC and encoder 1 (from SW 4.1)
6
Standard telegram 6, n set interface 32 bit with DSC and encoder 1 and encoder 2
(from SW 4.1)
101
The frame has the same structure as in SW 2.4
102
Standard frame 102, n-set interface with encoder 1
103
Standard telegram 103, speed setpoint interface with encoder 1 and encoder 2
(from SW 3.3)
104
Standard frame 104, n-set interface with encoder 1 and encoder 3
105
Standard telegram 105, n-set interface with DSC and encoder 1 (from SW 4.1)
106
Standard telegram 106, n-set interface with DSC and encoder 1 and encoder 2
(from SW 4.1)
107
Standard telegram 107, n-set interface with DSC and encoder 1 and encoder 3
(from SW 4.1)
108
Standard telegram 108, master drive for the position reference value coupling
(from SW 4.1)
109
Standard telegram 109, slave drive for the position reference value coupling
(from SW 4.1)
110
Standard telegram 110, positioning in the MDI mode (from SW 7.1)
Note: refer to the index entry ”Process data configuring”
0923:300 List of PROFIBUS standard signals
Min
Standard
Max
Unit
Data type
Effective
–
–
–
–
Unsigned16
RO
This parameter can be read in order to define which PROFIdrive standard signals (signals
1...99) and manufacturer-specific signals are supported and which device-specific signal ID this
signal represents.
Note:
If this parameter is read via non-cyclic communication (PROFIdrive), then the indices have
been shifted. Index 1 corresponds to Index 0 (etc.) in the description of the PROFIdrive profile.
A Lists
01.99