6
6.3
Axis couplings (from SW 3.3)
6-465
Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
The following parameters should be set:
P0922 = 0
In the example, the standard telegram 102 is extended by MsollExt.
––> the telegram should be configured as follows:
PZD1
STW1
ZSW2
PZD1
ZSW1
PZD 4
Setpoint
Actual
point
PZD 4
STW2
PZD 5
MomRed
MeldW
PZD 5
P0915
:1
50001
P0915
:4
50003
P0916
:1
50002
P0916
:4
50004
P0916
:5
50102
P0915
:5
50101
PZD2
PZD 3
NSOLL_B
P0915
:2
50007
P0915
:3
50007
PZD2
PZD 3
NIST_B
P0916
:2
50008
P0916
:3
50008
PZD 6
MsollExt
P0915
:6
50113
Fig. 6-45 Configuring a telegram, slave drive
P0915:6 = 50113 ––> control word MsollExt
P0916:6 ... 10 = 0 ––> disables the encoder interface (optional)
Note
The normalization at the master and slave drive can be influenced
using P0882.
The following parameters are available for the ”torque setpoint cou-
pling” function:
P0607
Analog setpoint, terminal 56.x/14.x
P0612
Analog setpoint, terminal 24.x/20.x
P0618
Normalization voltage, speed setpoint
P0619
Normalization voltage, torque setpoint
P0620
Normalization voltage, torque/power reduction
P0882
Evaluation, torque setpoint PROFIBUS
P0881
Evaluation, torque/power reduction PROFIBUS
P0916
PZD actual value assignment, PROFIBUS
P0922
Telegram selection PROFIBUS
P1240:8
Offset, torque setpoint (closed–loop speed–controlled)
P1241:8
Normalization, torque setpoint
P1242:8
Offset, torque setpoint (open–loop torque–controlled)
P1243:8
Normalization, torque/power reduction
P1252
Transition frequency, torque setpoint smoothing
P1725
Normalization, torque setpoint
Parameterizing
the slave drive
Parameter
overview
(refer to Chapter
A.1)
6 Description of the Functions
01.99
08.01