6
6.4
Input/output terminals of the control board
6-513
Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
Table 6-49
List of output signals, continued
Operating
mode
Signal name, description
PROFIBUS bit
pos
n–set
Fct. No.
Control via PROFIBUS (from SW 3.1)
38
x
x
PZD
”DIG_OUT”
The output terminal with this function can be controlled via PROFIBUS.
In this case, process data has to be configured, and then signal 50107 assigned to the PZD to be con-
trolled in the setpoint telegram (digital outputs, terminals O0.x to O3.x, DIG_OUT).
The following definitions apply:
Assigning the function
to the terminal
Parameterizing the control using
Term. O0.x
––> P0680 = 38
Bit 0 from PZD ”DIG_OUT”
Term. O1.x
––> P0681 = 38
Bit 1 from PZD ”DIG_OUT”
Term. O2.x
––> P0682 = 38
Bit 2 from PZD ”DIG_OUT”
Term. O3.x
––> P0683 = 38
Bit 3 from PZD ”DIG_OUT”
Note:
P0699 (inverting output terminals) can be used to set the output signal inversion by the drive.
Refer to Chapter 5.6.5 for information on configuring process data.
Status, block selection 1st output/2
0
2nd output/2
1
3rd output/2
2
4th output/2
3
5th output/2
4
6th output/2
5
50
51
52
53
54
55
x
x
x
x
x
x
x
x
x
x
x
x
AktSatz.0
AktSatz.1
AktSatz.2
AktSatz.3
AktSatz.4
AktSatz.5
These output signals are used to display which traversing block is being presently processed.
Block number
0
1
2
3
4
5
...
31
...
63
1st output/weighting 2
0
0
1
0
1
0
1
...
1
...
1
2d output/weighting 2
1
0
0
1
1
0
0
...
1
...
1
3rd output/weighting 2
2
0
0
0
0
1
1
...
1
...
1
4th output/weighting 2
3
0
0
0
0
0
0
...
1
...
1
5th output/weighting 2
4
0
0
0
0
0
0
...
1
...
1
6th output/weighting 2
5
0
0
0
0
0
0
...
0
...
1
Ready to be powered–up/not ready to be pow-
ered–up
–
x
x
ZSW1.0
The output signal indicates whether the drive is ready to be powered–up.
1 signal
Ready to power–up
In order that the drive goes into this state, the following conditions must be fulfilled:
– the two operating conditions are available via STW1 (xxxx xxxx xxxx x11x)
– the following enable signals are available: Terminal 63 (NE module), terminal 663
– No fault present
– No power–on inhibit present
0 signal
Not ready to be powered–up
The drive is not ready to be powered–up.
No OFF 2 present/OFF 2 present
–
x
x
ZSW1.4
1 signal
No OFF 2 present
0 signal
OFF 2 present
6 Description of the Functions
01.99
! 611ue diff !
08.01