Input/output terminals of the control board
6-479
Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
Table 6-45
List of input signals, continued
Operating
mode
Signal name, description
PROFIBUS bit
pos
n–set
Fct. No.
Ramp–up time zero
7
x
x
STW2.4
The ramp–function generator (RFG) can be switched–in and out via this input signal.
1 signal
Ramp–function generator off
This acts just like a ramp–up and ramp–down of the ramp–function generator of 0 ms.
0 signal
Ramp–function generator on
Integrator inhibit, speed controller
8
x
x
STW2.6
The integral component of the speed controller can be inhibited or enabled using this input signal.
1 signal
Integrator inhibit, speed controller
0 signal
The speed controller integrator is not inhibited
Note:
For a 1 signal, the integral component of the speed controller is deleted (cleared) and the integrator is
inhibited.
Parameter set changeover
1st input/2
0
2nd input/2
1
3rd input/2
2
9
10
11
x
x
x
x
x
x
STW2.0
STW2.1
STW2.2
It is possible to toggle between a total of 8 parameter sets using these 3 input signals.
Parameter set
0
1
2
3
4
5
6
7
1st input/weighting 2
0
0
1
0
1
0
1
0
1
2nd input/weighting 2
1
0
0
1
1
0
0
1
1
3rd input/weighting 2
2
0
0
0
0
1
1
1
1
Standard
setting
Note:
The bits, which are not assigned to an input terminal, are treated just like a 0 signal.
To change over, e.g. from parameter set 0 to 1, only the signal of the 1st input is necessary.
In order to ensure that the function changes over in a controlled fashion (identified as being simulta-
neous) the switching operation of the inputs must be completed with one interpolation clock cycle
(P1010).
The ”parameter set changeover” function is described in Chapter 6.10.