The following parameters are available for the ”teach–in” function:
P0120
Teach–in block
P0121
Teach–in standard block
P0124
Teach–in configuration
The following signals are used for the ”teach–in” function:
Input signals
(refer under index entry ”Input signal, digital – ...”)
– Input signal ”activate teach–in (edge)”
––> using an input terminal with function number 64
––> using the PROFIBUS control signal ”PosStw.6”
– Input signal ”block selection 1st to 6th input”
––> using an input terminal with function number 50 – 55
––> using PROFIBUS control signal SatzAnw.0 – .5
Output signals
(refer under the index entry, ”Output signal, digital – ...”)
– Output signal ”teach–in successful”
––> using an output terminal with function number 64
––> using the PROFIBUS status signal ”PosZsw.15”
Note
The positions with teach–in are only transferred into the RAM memory.
Data is manually saved using the ”SimoCom U” parameterizing and
start–up tool with ”Save in the drive (FEPROM)”.
Parameter
overview
(refer to Chapter
A.1)
Input/output
signals (refer to
Chapter 6.4)
6 Description of the Functions
01.99
! not 611ue !
06.04