2.2.3
Connecting–up the power module
Table 2-2
Overview of the interfaces
Terminals
Function
Type
1)
Technical data
No.
Desig-
nation
1)
Motor connections
U2
V2
W2
A1
Motor connection
for drive A
O
Note:
Additional information on connecting–up the power
module, technical data as well as interface over-
view are included in:
U2
V2
W2
A2
Motor connection
for drive B
(only for 2–axis
power modules)
O
view are included in:
Reference: /PJU/ SIMODRIVE
611
Configuration Manual,
Drive Converters
Chapter ”Power module”
PE
Protective conductor
I
0 V
Screw
DC link
P600
M600
–
DC link
IO
Busbar
Equipment bus
–
X151
Equipment bus
IO
Ribbon cable:
34–pole
Voltages: various
Signals:
various
1) O: Output; I: Input; IO: Input/output
!
Warning
If a contactor is used between the motor and the power module, then it
must be ensured that this contactor is only switched in a no–current
condition (power circuit).
Powering–down:
When terminal 663 (pulse cancellation) is simultaneously de–energized
and the coil of the power contactor, this condition is maintained. The
pulses are almost instantaneously canceled, the contactor contacts are
then in a no–current condition, and switch somewhat later due to the
contact delay.
Powering–up:
Terminal 663 may only be energized if all of the main contacts of the
power contactor are closed (e.g. terminal 663 is switched through an
auxiliary contact of the power contactor).