P0892 cannot be used with this measuring system
Cause
The following settings are permitted (Order No.[MLFB] 6SN1118–.... ):
Incremental measuring systems ( 7 bit ) with sin/cos 1 Vpp without En-
Dat interface (..*NH00–0AA*, ..*NH10–0AA*) : 0
Incremental measuring systems ( 7 bits ) with sin/cos 1 Vpp with EnDat
interface (..*NH00–0AA*, ..*NH10–0AA*) : 0,1,2,3
Incremental measuring systems ( 11 bit ) with sin/cos 1 Vpp
(..*NH01–0AA*, ..*NH11–0AA*) : 0,1,2,3,4
resolver ( 12 bit ) (..*NK00–0AA0 or ..*NJ00–0AA0) : 0,1,2,3
Resolver ( 12 bit ) (..*NK01–0AA0 or ..*NJ01–0AA0) with 12-bit resolu-
tion ( 1011[2]=0 or 1030[2]=0 ) : 0,1,2,3,4,5
Resolver ( 14 bit ) (..*NK01–0AA0 or ..*NJ01–0AA0) with 14 bit resolu-
tion ( 1011[2]=1 or 1030[2]=1 ) : –2,–1,0,1,2,3
Remedy
Set P0892 (factor, angular encoder pulse number/encoder pulse num-
ber) to a valid value.
Acknowledgement POWER ON
Stop response
STOP II (SRM, SLM) STOP I (ARM)
762
P0893 cannot be used with this measuring system
Cause
For incremental measuring systems with sin/cos 1 Vpp without EnDat
interface and for linear measuring systems with sin/cos 1 Vpp with En-
Dat interface, a zero pulse offset cannot be set via P0893.
Remedy
Set P0893 (angular encoder zero pulse offset) to 0.
Acknowledgement POWER ON
Stop response
STOP II (SRM, SLM) STOP I (ARM)
764
Multiple assignment of terminal A or B (P0890)
Cause
When selecting 3 in P0890, from drive A or B (setpoint at terminal A
and actual value at terminal B), it was identified, that terminal A or B
were already being used by another drive. Thus, this configuration is
not possible.
Remedy
Check the configuration of terminals A and B in P0890 and eliminate
multiple assignments of both drives.
Acknowledgement POWER ON
Stop response
STOP II (SRM, SLM) STOP I (ARM)
765
P0890 and P0891 configure both setpoint inputs
Cause
An actual value coupling is switched in (P0891 = 1) for drive B. Simul-
taneously, for the same drive, terminal A or B is parameterized as posi-
tion setpoint input (P0890 = 2 or 3).
Remedy
Check the configuration of terminals A and B in P0890, compare with
P0891 and eliminate multiple setpoint sources.
Acknowledgement POWER ON
Stop response
STOP II (SRM, SLM) STOP I (ARM)