1
1.3
”SIMODRIVE 611 universal” control board
1-38
Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
Reader’s note
The display and operator control elements provided on the front panel
are described in the following.
Additional information about
Terminals (assignment, wiring, technical data, etc.)
Interfaces (assignment, wiring, etc.)
are included in the Chapter 2.
The component comprises a button with integrated LED.
POWER–ON RESET, button
The button is recessed into the front panel (hole:
∅
3 mm).
The processor runs up again when pressed.
When the pushbutton is pressed, an LED which may have been pre-
viously bright (lit), goes dark, i.e. this indicates the pushbutton was
completely actuated (the pushbutton pressure point has been
reached).
!
Warning
When the POWER–ON RESET button is pressed, this corresponds to
a POWER ON and should only be executed when the motors are at a
standstill.
In order to prevent the drive from undesirably starting after POWER
ON, before carrying out a POWER ON–RESET, the controller enable
must be withdrawn at terminals 65.A and 65.B.
FAULT, LED red
(refer to Chapter 7.2.2)
The LED is bright at run–up and when faults occur.
The 6–character 7–segment display with point is used to display and
change parameter values and to display alarms.
The operator control PLUS, P and MINUS keys are used to select and
change parameter values and/or for operator control when faults and
warnings are displayed (e.g. to acknowledge these).
Reader’s note
Handling the display and operator unit
How to parameterize ”SIMODRIVE 611 universal” is described in
Chapter 3.2.
To remove faults and warnings refer to Chapter 7.2.
Button for
POWER
ON–RESET,
FAULT, LED red
Display
and
operator unit
1 Product Overview
01.99
! 611ue diff !